Comparative Analysis on Experiment about Open loop System and Close loop System of WSHP at Yangtze River
WANG Yong,GU Ming,XIAO Yi min,HAN Chuan pu,LAI Dao xin and WANG Zi yun
DOI:10.11835/j.issn.1674-4764.2009.02.024
Received ,Revised , Accepted , Available online July 01, 2015
Volume ,2009,Pages 126-130
- Abstract
Yangtze River is abundant of water and can provide enough water as cooling and heating source for water source heat pumps (WSHP). A pair of contrast experiments with open loop system and close loop system of WSHP were finished in order to get the heat pump's COP, the system's COP and the distribution of water temperature in the heat exchanger etc. This paper compared the characteristic and the COP of these two kinds of system. The heat pump's COP of the open loop system and close loop System are 3.08 and 3.77 respectively, and the system's COP are 2.83 and 2.80 respectively. At last, applications of open loop system and close loop System of WSHP at Yangtze River were analyzed and the key problem for attention was pointed out in the paper.